NSW Legionella Taskforce: Changes to regulations in 2018

NSW Health recently announced changes to the Public Health Regulation from 1st January 2018, with further changes to follow in early 2018.

After two outbreaks of Legionnaires Disease in March and May of 2016 an expert panel convened by the Chief Health Officer and subsequent discussion paper led to the formation of the Legionella Taskforce in February 2017.

Recommendations passed down from the taskforce reflected the Victorian regulatory regime and led to the development of ‘Six Safeguards’ which form the basis of changes to NSW public health regulations concerning cooling towers:

  • Risk Management Plans (RMPs) developed every five years (or once every year for high risk systems)
  • Independent auditing conducted every year
  • Certificate of RMP completion & audit completion lodged with local council
  • Laboratory testing for Legionella and heterotrophic colony count every month
  • Notification of elevated laboratory tests to local council
  • Unique identification number to be displayed on every cooling tower

As the incidence on legionella is significantly higher in the summer months it was decided that mandatory monthly testing of cooling towers should commence in January 2018 (many properties would already be conducting monthly testing).

The remaining requirements will be staged throughout the rest of the year to allow time for local councils and industry to prepare.

As part of the monthly cooling tower testing the occupier of the premises as defined by NSW Health (more details on these definitions can be found here) must notify the local council of elevated Legionella count (≥1000 cfu/mL) or HCC (≥5,000,000 cfu/mL).

Risk management plans are to be reviewed every 5 years however for higher risk systems the requirement will be a review on an annual basis. The definition of high risk system is yet to be announced though we believe it will be all buildings in higher density business districts for example Sydney, North Sydney and Parramatta.

Guidelines for developing risk management plans will be provided by NSW Health in early 2018, though we expect requirements to be similar to other States where QED has experience developing such plans for its customers. QED cooling tower risk management includes access to our customised online service.

If you would like more information on how these regulatory changes impact management of your cooling towers we welcome you to contact us.


Recent Posts

Trichloramine and Indoor Air Quality in Swimming Pools

05th Nov

For swimmers and pool workers alike, the characteristic "chlorine smell" at indoor swimming pools is part of the experience. Howev...

Indoor Air Quality Takes Centre Stage: A New Government Report on Airborne Virus Transmission

30th Sep

The importance of Indoor Air Quality (IAQ) has gained significant attention following the release of a groundbreaking report from Australiaâ...

Changes to the workplace exposure standard for welding fumes

15th Mar

On January 18, 2024, SafeWork Australia made a significant adjustment to the Workplace Exposure Standard (WES) for Welding Fume (not otherwi...

View All
QED FEATURED ARTICLES

How IEQ Impacts Employee Productivity

We believe tenants should engage with landlords on the indoor environment quality with the same level of importance at which they consider the energy consumption of a building – it will improve their bottom line faster!

White Papers

October 27th 2023

Clearing the Air: A case study on managing the risk of lead dust

A case study on how we saved a customer thousands of do...

December 13th 2021

The Impact of Indoor Environment Quality on Cognitive Function

As we head into 2022, a year marked by the great migrat...

September 07th 2021

Using Ventilation to Reduce the Covid-19 Infections within Hospitals

Using Ventilation to Reduce the Covid-19 Infections wit...

View More

Latest News

November 05th 2024

Trichloramine and Indoor Air Quality in Swimming Pools

For swimmers and pool workers alike, the characteristic...

September 30th 2024

Indoor Air Quality Takes Centre Stage: A New Government Report on Airborne Virus Transmission

The importance of Indoor Air Quality (IAQ) has gained s...

March 15th 2024

Changes to the workplace exposure standard for welding fumes

On January 18, 2024, SafeWork Australia made a signific...

View More

Need more information? We’re here to help you...

Get in touch